LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 1 12.16.2015
LP Dimming Panels
LP dimming panels are ideal for projects with many
small loads. Each panel provides power and dimming
for up to 32 controllable outputs.
Features
Works directly with incandescent, magnetic
low‑voltage, and neon/cold cathode lighting, as well as
Lutron® TuWire® fluorescent dimming ballasts.
Works with electronic low‑voltage lighting via power
interfaces.
Works with 3‑wire AC motors through motor modules.
Panels are prewired just bring in feed and load
wiring.
Surface or recess mount between 16 in (40 cm)
centerto‑center studs.
Models available with:
120 V~, 220 – 240 V~ (non CE), or 230 V~ (CE) input
power.
1 8 dimming modules for 4 32 controllable outputs.
Different feed types and breakers.
LP Dimming Panels work with:
GRAFIK Eye® 4000 control units.
• QuantumR systems.
GP dimming panels and XP switching panels.
DMX512 dimming systems via the 2LinkTM option.
Mini LP Dimming Panel
LP1/4 – LP3/12
Standard‑Size LP Dimming Panel
LP4/28 – LP8/32
1
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 2 12.16.2015
Dimming Modules**
Each dimming module can handle a fully loaded
electrical circuit, up to four controllable outputs per
module.
Maximum Ratings
Voltage Capacity per
Dimming Module
Capacity per
Dimming Leg
120 V~ 16 A 16 A
220 – 240 V~ (nonCE) 16 A 16 A
230 V~ (CE) 13 A 10 A
• RTISSTM filter circuit technology compensates for
incoming line voltage variations: No visible flicker with
+/2% change in RMS voltage/cycle and +/2% Hz
change in frequency/second.
Wiring
Internal: Prewired by Lutron.
System communications: Low‑Voltage
IEC PELV/ NEC® Class 2 wiring connects dimming
panels to other components.
Line (mains) voltage: Feed and load wiring only. No
other wiring or assembly required.
Setup
Circuit selector electronically assigns controllable
outputs to zones and sources; permits reassignment
of zones and sources without rewiring.
Physical Design
Enclosure: NEMA‑Type 1, IP‑20 protection; 16 U.S.
gauge steel. Indoor use only.
Weight: 27 lb (13 kg) for Mini LP, 63 lb (29 kg) for
Standard‑Size LP.
Seismic Certification Limits: SDS = 2.5 g, z/h = 1.0,
IP = 1.5. Contact Lutron for details.
Mounting
Surface mount or recess mount between 16 in (40 cm)
studs.
Allow space for ventilating.
Environment
32 104 °F (0 40 °C). Relative humidity less than
90%, non‑condensing.
Specifications
Regulatory Approvals (120 V~ panels only)
UL Listed (Reference: UL File 42071).
Complies with CSA, NOM, or CE (where appropriate.
Contact Lutron for listing details on custom panels).
Seismic certified panels can be provided upon
request. Contact Lutron for details.
Power
Input power: 120 V~, 220 – 240 V~ (non CE), and
230V~ (CE). All voltages 50/60 Hz, phase‑to‑neutral.
Branch circuit breakers (AIC ratings):
120 V~ 10,000 A
220 – 240 V~ 6000 A
230 V~ (CE) 6000 A
Lightning strike protection: Meets ANSI/IEEE standard
62.411980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10‑year power failure memory: Automatically restores
lighting to scene selected prior to power interruption.
Short-Circuit Current Ratings (other ratings
available)
Panel Type Voltage Standard SCCR Rating
LP Main Lug Panels
(all sizes)
120 V~ 25,000 A
Sources/Load Types
Operates these sources with a smooth, continuous
Square Law dimming curve or in a full‑conduction,
non‑dim state:
Incandescent (Tungsten/Halogen).
Magnetic LowVoltage transformer.
• Lutron® TuWire® electronic fluorescent dimming
ballasts.
Neon/Cold Cathode.
Operates these sources via power interfaces:
Leading edge Electronic LowVoltage transformer via
dedicated internal dimming modules or external power
interfaces.
• Lutron® electronic fluorescent dimming ballasts via
external power interfaces.
Operates HID sources in a full conduction, non‑dim
state.
• LED and Compact Fluorescent*
* Not all LED and CFL loads available today are dimmable. Visit www.lutron.com/LEDtool for a list of loads that have been tested by Luton to be
compatible with this product.
** For more information on load ratings, please refer to Application Note #201 at www.lutron.com/TechnicalDocumentLibrary/048‑201.pdf
2
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 3 12.16.2015
How to Build an LP Dimming Panel Model Number
Prefix
LP: Dimming Panel
Number of Dimming Modules
Indicates number of dimming modules in the panel. Also indicates number of full load circuits.
Number of Controllable Outputs
Indicates number of controllable outputs in the panel. Each module has four controllable outputs.
Voltage
120: 120 V~
230: 230 V~ (CE)
240: 220 – 240 V~ (nonCE)
Feed Type
2: 1‑phase 2‑wire
3: 1‑phase 3‑wire (split‑phase)
4: 3‑phase 4‑wire
Panel Feed
ML: Main Lugs only
Mxx: Main Breaker with xx = breaker size in Amps (custom panel option)
IS: Isolation Switch (CE/non‑CE only)
Branch Circuit Breaker Rating
20: 20 A branch circuit breakers (120 V~ only)
15: 15 A branch circuit breakers (120 V~ only)
13: 13 A branch circuit breakers (230 V~ CE only)
16: 16 A branch circuit breakers (240 V~ non‑CE only)
Custom Panel Suffix
CGP number indicates specific characteristics of a customized panel.
Prefix Number
of
Dimming
Modules
Number of
Controllable
Outputs
Voltage Feed
Type
Panel
Feed
Branch
Circuit
Breaker
Rating
Custom
Panel
Suffix
L P 7 / 2 8 1 2 0 4 M L 2 0 C G P _ _ _
3
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 4 12.16.2015
Models
Only standard panels listed. Consult Lutron for further options.
Mini LP Dimming Panels
120 V~ Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
LP1 4
2W 20 A
15 A or
20 A
1
branch
circuit
breakers
LP2 8
2W 40 A
3W 20 A
LP3 12
2W 40 A
3W 40 A
3Ø 4W 20 A
1
20/16 A, 15/12 A continuous load rating.
220 – 240 V~ (non-CE) Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
LP1 4
2W 16 A
16 A
branch
circuit
breakers
LP2 8
2W 32 A
LP3 12
2W 48 A
3Ø 4W 16 A
230 V~ (CE) Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
LP1 4
2W 13 A
13 A
branch
circuit
breakers
LP2 8
2W 26 A
LP3 12
2W 39 A
3Ø 4W 13 A
Wire Sizes
Feed Wiring
Power (Hot/Live) connects directly to branch circuit breakers:
120 V~: 14AWG to 10AWG (2.0mm
2
to 4.0mm
2
)
220 – 240 V~ (non‑CE): 18AWG to 4AWG (1.0mm
2
to 25mm
2
)
230 V~ (CE): 18AWG to 4AWG (1.0mm
2
to 25mm
2
)
Neutral connects to neutral lug:
120 V~: 14AWG to 2/0AWG (2.0mm
2
to 70mm
2
)
220 – 240 V~: 14AWG to 8AWG (2.0mm
2
to 6.0mm
2
)
230 V~ (CE): 14AWG to 8AWG (2.0mm
2
to 6.0mm
2
)
Load Wiring
All Models: 14AWG to 10AWG (2.0mm
2
to 4.0mm
2
)
4
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 5 12.16.2015
Models (continued)
Only standard panels listed. Consult Lutron for further options.
Standard-size LP Dimming Panels
120 V~ Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
Branch
Circuit Breakers
LP4 16 3Ø 4 W 175 A
Main
lugs only
15 A or 20 A
1
LP5 20 3Ø 4 W 175 A
LP6 24 3Ø 4 W 175 A
LP7 28 3Ø 4 W 175 A
LP8 32 3Ø 4 W 175 A
1
20/16A, 15/12A continuous load rating.
220 – 240 V~ (non-CE) Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
Branch
Circuit Breakers
LP4 16 3Ø 4 W 125 A
Isolation
switch
only
16 A
LP5 20 3Ø 4 W 125 A
LP6 24 3Ø 4 W 125 A
LP7 28 3Ø 4 W 125 A
LP8 32 3Ø 4 W 125 A
230 V~ (CE) Power
Number of
Dimming Modules
Number of
Controllable Outputs
Feed
Type
Maximum
Feed
Panel
Feed
Branch
Circuit Breakers
LP4 16 3Ø 4 W 125 A
Isolation
switch
only
13 A
LP5 20 3Ø 4 W 125 A
LP6 24 3Ø 4 W 125 A
LP7 28 3Ø 4 W 125 A
LP8 32 3Ø 4 W 125 A
Wire Sizes
Feed Wiring to Main Lugs (120 V~ Only):
Power (Hot/Live): (3) 14 AWG to 2/0 AWG (2.0 mm
2
to 70 mm
2
)
Neutral: (1) 14 AWG to 2/0 AWG (2.0 mm
2
to 70 mm
2
)
Feed Wiring to Isolation Switch
(CE/non‑CE only):
Power (Hot/Live): (3) 2.5 mm
2
to 35 mm
2
Neutral: (1) 2.5 mm
2
to 35 mm
2
Load Wiring
All Models: 14 AWG to 10 AWG (2.0 mm
2
to 4.0 mm
2
)
5
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 6 12.16.2015
Dimensions
All dimensions shown as: in (mm)
Mini LP Dimming Panels
Top View
14.38
(365.25)
Bottom View
4.09
(103.84)
Right Side View
4.14 (10 5.36)
0.15 ( 3.81)
Left Side View
24.00
(609.6)
Front View
15.875
(403.23)
15.13
(384.3)
21.50
(5 4 6.1)
24.50
(622.3)
2.21 (56.05)
2.21 (56.05)
1.34 (33.94)
8.00
(203.20)
10.75
(273.05)
Cover
6
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 7 12.16.2015
Dimensions (continued)
All dimensions shown as: in (mm)
Standard-size LP Dimming Panels
Top View
14.375
(3 6 5.13)
Bottom View
2.69
(68.25)
Front View
15.875
(403.23)
15.125
(3 9 4.18)
41.75
(1060.45)
59.50
(1511.30)
2.43 (61.85)
2.43 (61.85)
2.69 (68.25)
8.00
(203.20)
11.0 0
(279.4)
Right Side View
4.21 (106.93)
0.15 ( 3.81)
Left Side View
59.50
(1511.30)
Cover
7
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 8 12.16.2015
Recess Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8 in (3 mm) below
finished wall surface.
Mounting
Mini LP Dimming Panels
Surface‑ or recess‑mount indoors.
• Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 32 – 104 °F (0 – 40 °C).
This equipment is aircooled. Do not block vents or
warranty will be void.
Mount panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Surface Mounting
Surface mounting keyholes accept 1/4 in (6 mm)
mounting bolts. This size is recommended.
Maximum Feed and Wire Sizes
Consult Wiring page.
Panel Maximum BTUs/hour Weight Without Packaging
LP1 90 33 lb (15 kg)
LP2 170 35 lb (16 kg)
LP3 250 37 lb (17 kg)
N
Front View Side View
Feed wiring
and
controllable
outputs to
loads
Branch
circuit
breakers
Feed wiring and
controllable
outputs to loads
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for controllable
outputs to loads
N
Front View Side View
Branch
circuit
breakers
Feed wiring
and
controllable
outputs to
loads
Feed wiring and
controllable
outputs to loads
IEC PELV/NEC
®
Class 2 wiring
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for controllable
outputs to loads
8
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 9 12.16.2015
Recess Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8 in (3 mm) below
finished wall surface.
Mounting (continued)
Standard-size LP Dimming Panels
Surface‑ or recess‑mount indoors.
Consult Dimensions page for dimensions and conduit
knockout locations.
Panel generates heat. Mount only where ambient
temperature is 32 – 104 °F (0 – 40 °C).
This equipment is aircooled. Do not block vents or
warranty will be void.
Reinforce wall structure for weight and local codes.
Mount Panels where audible noise is acceptable.
(Panels hum slightly and internal relays click.)
Mount Panels so line (mains) voltage wiring is at least
6 ft (1.8 m) from sound or electronic equipment and
wiring.
Mount Panel within 7° of true vertical.
Surface Mounting
Surface mounting keyholes accept 1/4 in (6 mm)
mounting bolts. This size is recommended.
Maximum Feed and Wire Sizes
Consult Wiring page.
Panel Maximum BTUs/hour Weight Without Packaging
LP4 330 55 lb (25 kg)
LP5 410 57 lb (26 kg)
LP6 490 59 lb (27 kg)
LP7 570 61 lb (28 kg)
LP8 650 63 lb (29 kg)
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring and
controllable
outputs to loads
Feed wiring and
controllable
outputs to loads
Preferred
feed wiring
IEC PELV/NEC
®
Class 2 wiring
Main lugs
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for controllable
outputs to loads
1
2
4
3
5
6
8
7
A
B
C
N
Front View Side View
Feed wiring and
controllable
outputs to loads
Preferred
feed wiring
IEC PELV/NEC
®
Class 2 wiring
Main lugs
Do not
block vents
12in (31cm)
minimum
clearance
Terminal blocks
for controllable
outputs to loads
9
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 10 12.16.2015
Wiring
Mini LP Dimming Panels
Wire the Mini LP panel similarly to a lighting distribution
panel:
Run feed and load wiring; no other wiring or assembly
is required.
Run separate neutrals for each module (no common
neutrals across phases).
The Mini LP panel can provide temporary lighting:
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Use branch circuit breakers to switch lights on and off.
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Bypass jumpers
(Do not remove
until load wiring
is verified)
Mini LP
(cover off)
Terminal blocks
Branch circuit breakers
Neutral lug
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Load
Power (Hot/Live) Wiring
120 V~
14 – 10 AWG (2.0 – 4.0 mm
2
)
220 – 240 V~
18 – 4 AWG (1.0 – 25 mm
2
)
230 V~ (CE)
Neutral Wiring
120 V~
14 – 2/0 AWG (2.0 – 70 mm
2
)
220 – 240 V~
14 – 8 AWG (2.0 – 6.0 mm
2
)
230 V~ (CE)
10
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 11 12.16.2015
Wiring (continued)
Standard-size LP Dimming Panels
Wire the LP panel similarly to a lighting distribution
panel:
Run feed and load wiring; no other wiring or assembly
is required.
Run separate neutrals for each module (no common
neutrals across phases).
The LP panel can provide temporary lighting:
Wire all loads.
Do not remove the bypass jumpers that protect the
dimming modules.
Use branch circuit breakers to switch lights on and off.
N
N
DH
H
DH
N
DH
DH
N
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
N
N
DH
H
DH
N
DH
DH
N
N
Power (Hot/Live) Wiring
(3) 14 – 2/0 AWG (2.0 – 70 mm
2
)
Neutral Wiring
(1) 14 – 2/0 AWG (2.0 – 70 mm
2
)
Bypass jumpers
(Do not remove
until load wiring
is verified)
Standard LP
(cover off)
Terminal blocks
Branch circuit breakers
Neutral lug
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Load
11
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 12 12.16.2015
Electronic Low-Voltage
Use Lutron® ELVI Electronic Low‑Voltage Interface.
Consult ELVI Specification Submittal for
more details.
N
N
DH
H
DH
N
DH
DH
N
N
Transformer
Load
Load Terminals
Dimmed
Hot/Live
Neutral
ELVI
Feed
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Typical Controllable Outputs for 120 V~
All Load Types except:
• Lutron® Hi‑lume® or Eco‑10 ®
(ECO‑Series) Fluorescent Dimming
Ballasts
Electronic Low‑Voltage
N
N
DH
H
DH
N
DH
DH
N
N
Load
Load Terminals
Dimmed Hot/Live
Neutral
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Lutron® Hi-lume® or Eco-10® (ECO-Series) Fluorescent Dimming Ballasts
Use Lutron® FDBI Fluorescent Dimming Ballast Interface.
N
N
DH
H
DH
N
DH
DH
N
N
Eco‑10 ® or
Hi Lume®
Load
Load Terminals
Dimmed
Hot/Live
Neutral
FDBI
Feed
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
12
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 13 12.16.2015
Typical Controllable Outputs for 220 to 240 V~ (non CE)
All Load Types except:
• Lutron® Hi‑lume® or Eco‑10 ®
(ECO‑Series) Fluorescent Dimming
Ballasts
Electronic Low‑Voltage
N
N
DL
L
DL
N
DL
DL
N
N
Load
Load Terminals
Dimmed Live
Neutral
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Electronic Low-Voltage
Use Lutron® ELVI Electronic Low‑Voltage Interface.
Consult ELVI Specification Submittal for
more details.
N
N
DL
L
DL
N
DL
DL
N
N
Transformer
Load
Load Terminals
Dimmed Live
Neutral
ELVI
Feed
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Lutron® Hi-lume® or Eco-10® (ECO-Series) Fluorescent Dimming Ballasts
Use Lutron® FDBI Fluorescent Dimming Ballast Interface.
N
N
DL
L
DL
N
DL
DL
N
N
Eco‑10 ® or
Hi Lume®
Load
Load Terminals
Dimmed Live
Neutral
FDBI
Feed
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
13
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 14 12.16.2015
Typical Controllable Outputs for 230 V~ (CE)
All Load Types except:
• Lutron® Hi‑lume® or Eco‑10 ®
(ECO‑Series) Fluorescent Dimming
Ballasts
Electronic Low‑Voltage
N
N
DL
L
DL
N
DL
DL
N
N
Load
Load Terminals
Dimmed Hot/Live
Neutral
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
Electronic Low-Voltage
Use Lutron® ELVI Electronic Low‑Voltage Interface.
N
N
DL
L
DL
N
DL
DL
N
N
Transformer
Load
Load Terminals
Dimmed
Hot/Live
Neutral
ELVI
Feed
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
(1) 14 – 10 AWG
(2.0 – 4.0 mm
2
)
14
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 15 12.16.2015
Low-Voltage IEC PELV / NEC® Class 2 Wiring (All Models)
System communications uses low‑voltage IEC PELV / NEC® Class 2 wiring.
Wiring must be daisy‑chained.
Wiring must run separately from line (mains) voltage.
GRAFIK Eye® 4000 System
IEC PELV / NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
Approved low‑voltage cable is available from Lutron
1
, Belden, and Liberty. These are approved with 22 AWG
(0.625 mm
2
) data link wires.
QuantumR System
IEC PELV / NEC® Class 2 wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (600 m).
If MUX‑RPTR interface and GRX‑CBL‑46L cable
1
is used, length may be up to 4000 ft (1200 m).
1
GRX‑CBL46L IEC PELV / NEC® Class 2 wiring cable is available from Lutron and contains:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.625 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line.
LP Panel
Control Unit
Control Interface
Wallstations
LP Panel
QuantumR
Hub
Refer to QuantumR Specification
Control Unit
Control Interface
Wallstations
15
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 16 12.16.2015
Notes
* Emergency power: The additional 18 AWG (1.0mm
2
) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency (essential)
lighting panel to “sense” when normal (non‑essential) power is lost. If more than one emergency lighting panel needs to sense from a specific normal
panel, a dedicated wire between each pair of normal (non‑essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit board of circuit selector. Connect the bare drain wires and cut off
the outside shield.
IEC PELV / NEC® Class 2
Terminal Connections
Each LowVoltage IEC PELV / NEC® Class 2 terminal
can accept only two 18 AWG (1.0 mm
2
) wires.
Two12AWG (2.5 mm
2
) conductors won’t fit. Connect
as shown, using appropriate wire connectors.
SELECT CIRCUIT
2
1
Circuit
Data A OK
Power
1234 5D
Common
24VF
W
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
IEC PELV / NEC® Class 2 Panel-to-Panel Wiring (All Models)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
Control Wiring
(2) 12 AWG (2.5 mm
2
)
1: Common
2: 24 VFW
To
additional
Power
Panels
LP Panel 1 LP Panel 2
To Lighting
Controls or
Processors
Shield/Drain
Shield/Drain
(1) 18 AWG (1.0 mm
2
)
5: Sense Line
1
Data Link
(1) shielded, twisted pair 18 AWG (1.0 mm
2
)
3: MUX
4: MUX
1
2
3, 4
5
1
2
3, 4
(4) 12 AWG (2.5 mm
2
)
16
LP Dimming Panels
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GRAFIK Systems® Power Equipment
369344d 17 12.16.2015
Options
Consult Lutron for ordering information and model numbers. Dimensions and wiring may change based on
options chosen.
Option Description Application
Double Lug
Sets
Allows multiple Panels to be fed from the same feed. A single feed and multiple LP Dimming
Panels are required.
Branch Circuit
Protection
Branch Circuit Breakers with higher AIC ratings than
those on standard Panels.
Panels can also have Branch Circuit Breakers with
special ratings such as:
• GFI (Ground Fault Interrupt)
• ELB (Earth Leakage Breaker)
• RCD (Residual Circuit Device).
Lutron
® Ten‑Volt
Module (TVM)
Allows Panels to operate fluorescent ballasts that
meet IEC 929 standards for 010 V control including:
• Lutron® TVE ballasts
• 010 V neon
• PWM fluorescent
Tridonic® DSI (Digital Serial Interface). The TVM can
sink or source 50 mA (typically 25 50 ballasts) on
each circuit.
Jobs with fluorescent ballasts that
require 010 V, PWM, or DSI control.
2Link
TM Allows a DMX512 theatrical console to operate
Dimming Panels’ load circuits.
Allows a GRAFIK Eye® 4000 Series to handle
128zones (2 links of 64 zones). The 2 links are
independent and do not communicate. Contact
Lutron for further details.
Control of architectural lighting from a
DMX512 theatrical console is required.
A mix of architectural and theatrical
lighting exists on the job.
17